
Navien NPE-A2 and NPE-S2 error codes
Find your code and the safe next step.
As an Amazon Associate I earn from qualifying purchases.
On this page
Quick answer
With gas odor, leave and call the gas supplier from a neighbor’s phone. Otherwise, find your code before resetting. Chromex kits suit confirmed descaling; ignition, vent and gas-setting faults need diagnosis.

Read the display before buying anything
Record the whole code and the model on the rating label. These common routes come from Navien’s NPE-2 user manual; the full chart keeps every documented code together.
Do not light an appliance, touch an electrical switch or use a phone inside. Call the gas supplier from a neighbor’s phone. If unreachable, call the fire department. Do not reset or unplug the heater while gas may be present.
Move everyone to fresh air and call 911 or the fire department from outside. Do not remain in the building to silence the alarm, inspect the vent or restart the heater.
Navien lists checking the main gas supply valve. With no gas odor, note its position for the service professional. Do not reopen a valve shut for an unknown reason, adjust gas pressure or order an igniter from this code alone.
Navien lists intake-filter cleaning. E012 also calls for a grounding check; E110 calls for an unobstructed exhaust. A filter task does not authorise vent disassembly or electrical repairs.
E016 and E030 list inlet-filter cleaning and flushing. E760 is a flushing/service alarm that calls for routine service. Confirm the needed work before selecting equipment; a kit cannot prove why the code appeared.
Use the complete Navien code matrix. If your code is absent, photograph it and contact Navien at 1-800-519-8794. Do not borrow a definition from another Navien series.
Three kits for a confirmed descaling job
These are equipment choices for planned maintenance, not fault-code repairs. Pick by valve access and by the cleaner you plan to use, after checking the installed service valves.


Chromex standard hose kit

Chromex kit, no solution
Product prices and availability are accurate as of the date/time indicated and are subject to change. Any price and availability information displayed on Amazon.com at the time of purchase will apply to the purchase of this product.
| Kit | Key specs | Pick it if | Skip it if |
|---|---|---|---|
| Chromex right angle hose kit | 1/6 HP pump, 5-gallon bucket, Two angled hoses, 1 qt solution | Descaling is the confirmed task, a straight connector has insufficient access, and you can identify the A and B service valves. | You only need to read a code, the service valves are missing, or the fault concerns ignition, vent insertion or gas settings. |
| Chromex standard hose kit | 1/6 HP pump, 5-gallon bucket, Two PVC-coated hoses, 1 qt solution | You have open access to the service ports and can identify the A and B service valves. | A wall prevents a straight connection, the heater is still hot, or you are trying to diagnose a recurring E003 by buying a flush kit. |
| Chromex kit with no solution (CXT1-1102) | 1/6 HP pump, two 6 ft steel hoses, bucket with lid (3.5 gal on Amazon, 5 gal on Chromex’s page), no solution | You already have the cleaning solution your installer or Navien support named, and you can identify the A and B service valves. | You want a cleaner in the box, or the bucket that arrives is under the 5 gallons Navien’s manual asks for and you have no other. |
Chromex right angle kit for a tight closet
Valve access and your cleaner decide the kit, so none of the three is scored against the others.
The right angle Chromex kit is the more useful configuration when a wall or closet side crowds the service ports. Its connectors turn the hose sideways at the valve. Choose it for that physical clearance problem, after checking that the valve handle and hose nut can still move freely.
Chromex lists a five-gallon bucket, a 1/6 HP submersible pump, two angled steel hoses and one quart of descaling solution. The bucket meets Navien’s five-gallon minimum. Capacity is a container requirement, not an instruction to fill the bucket to its rim.
Navien’s drawing shows three hoses because it uses a pump outside the bucket. One hose only feeds that pump. The Chromex pump sits in the bucket, so its two hoses do the other two jobs: pump outlet to the cold-side “B” valve, and the hot-side “A” valve back to the bucket.
Where it does well
- Right angle connectors route hoses sideways at the valve
- Maker lists a five-gallon bucket and pump grate
- Pump and two hoses supplied together
What to watch
- Needs A and B service valves already on the heater
- Included solution needs installation-specific confirmation
- Angled connectors still need working clearance
Before either hose goes on, Navien has you turn off and unplug the heater, then close the “C” and “D” valves. That isolates the heater from the house plumbing during the flush.
Treat the included chemical as another decision to confirm. Chromex markets the kit for Navien, but Navien’s NPE-2 manual does not name this solution or give a dilution ratio. Follow the heater’s applicable instructions and the cleaner label, with its ventilation and protective-equipment precautions.
The timing also comes from the heater. Chromex advertises a thirty-minute flush, while Navien specifies at least forty-five minutes of circulation and a five-minute water rinse. A convenient hose angle does not shorten those instructions. Stop and call a licensed professional if you cannot identify the isolation valves.
My call: choose the angled kit for a confirmed maintenance job with obstructed straight access. Leave the panel settings alone. For E773 or E788, give the complete display and rating-label information to the service professional before any equipment choice. Neither code establishes a need for descaler.
Chromex standard kit for open valves
The standard Chromex kit fits the less crowded installation: both service connections can accept a hose without a sharp bend against a cabinet or wall. Chromex’s comparison describes hose angle as the difference between its standard and angled kits. Open access gives you no particular reason to choose an elbow.
Its current product page lists a five-gallon bucket, a 1/6 HP submersible pump, two PVC-coated hoses, one quart of solution and a raised pump grate. Check those contents against the particular box and instructions before starting. A familiar brand name does not resolve differences between kit variants.
Navien’s manual makes the bucket size easy to assess, and its pump drawing maps cleanly. Its three-hose list includes a pump-inlet hose that a submersible pump does not need. Connect the pump outlet to valve B and run valve A back to the bucket, as in steps 4 and 5.
Where it does well
- Standard hose layout suits unobstructed service ports
- Five-gallon bucket meets the manual’s capacity minimum
- Maker includes a pump grate
What to watch
- Straight access is needed at the valve connection
- Works only where A and B service valves are installed
- Thirty-minute marketing does not replace Navien’s timing
Descaling belongs after the fault assessment. E016 and E030 point to water-filter cleaning and flushing in the code table. E760 calls for routine service. Those entries make maintenance relevant; they do not prove that the supplied chemical is approved or that flushing will cure every recurrence.
Before maintenance, Navien requires shutdown, disconnected power and time to cool. Water-filter work also begins with draining under the manual’s gas and water shutoff procedure. If those valves are unfamiliar, stop. Do not disconnect a hot service port to discover whether the water is still under pressure.
My call: use the standard layout when its straight connectors have room, after the maintenance setup is checked. Keep the manual’s circulation and rinse instructions with the kit. If an overheat code returns after the prescribed service, call Navien or a licensed professional instead of repeating chemical cycles.
Chromex kit when you bring the cleaner
The CXT1-1102 is the pick when you already know which cleaner to use. Navien’s NPE-2 manual asks for a cleaning solution diluted with water and doesn’t name a brand. This Chromex kit comes without one, so nothing in the box pushes you toward a product your installer didn’t choose.
Chromex’s product page lists a bucket with lid, a 1/6 HP submersible pump and two 6 ft steel hoses, and says to add 2 to 3 gallons of white vinegar or your own descaler. The pump sits in the bucket, so the two hoses cover the A-valve drain and the feed to valve B.
One detail doesn’t match. The Amazon listing says the bucket is 3.5 gallons, and Chromex’s own page says 5 gallons. Navien’s manual asks for a bucket of 5 gallons or larger. Check the one that arrives before you start.
Where it does well
- No cleaner to set aside
- Steel hoses, 6 ft each
- 1-year warranty on the Amazon listing
What to watch
- You buy the cleaner separately
- Bucket size differs, 3.5 vs 5 gal
- Amazon gives 30 minutes; Navien says 45
If the bucket is the 3.5 gallon size, set it aside and use a 5-gallon pail. The pump and hoses work the same in either. The point of Navien’s minimum is room for the solution plus what drains back from the heat exchanger.
Ask whoever services the heater which cleaner suits a stainless heat exchanger before you pour anything. Chromex’s page suggests vinegar or a citric acid descaler. Navien’s manual only says diluted cleaning solution, and it’s the manual that decides.
Run the pump for at least 45 minutes, as Navien’s §4.3 says, even though the Amazon listing says 30. For the rinse, the manual says close B and open D with C still closed, let water run for 5 minutes, then close A and open C.
Like the other two kits, this one only helps with scale. It won’t clear an ignition, vent or gas-setting code. Read the code table first, and flush only when the display or the service schedule points to descaling.
Compare the equipment against Navien’s procedure
The heater’s instructions control the maintenance job. Match the kit to the service valves on your heater.
| Kit and product photo | Use | Maker-listed contents | Advantage | Limit | Amazon |
|---|---|---|---|---|---|
Chromex right angle hose kit | Restricted straight access | 5-gallon bucket; 1/6 HP pump; two angled hoses; 1 qt solution | Hose exits sideways | Confirm pump arrangement and chemical | Check it on Amazon |
Chromex standard hose kit | Open valve access | 5-gallon bucket; 1/6 HP pump; two PVC-coated hoses; 1 qt solution | No elbow needed for open access | Straight connector needs room | Check it on Amazon |
Chromex kit, no solution | Your own named cleaner | Bucket with lid; 1/6 HP pump; two 6 ft steel hoses; no solution | Nothing to set aside if your cleaner differs | Bucket size differs between listing and maker | Check it on Amazon |
Navien does not approve either kit’s cleaner by name. Check the cleaner label against your heater before use.
| Where claims differ | Chromex description | Navien NPE-2 manual | Use this rule |
|---|---|---|---|
| Circulation time | Advertises a flush in 30 minutes | At least 45 minutes of solution circulation | Do not shorten Navien’s circulation time to the kit’s marketing claim. |
| Rinse | General kit guidance | Five-minute water rinse in §4.3 | Follow the heater’s valve sequence and rinse instructions. |
| Hoses and pump | Two hoses; submersible pump | Three hoses; drawing shows a separate pump inlet | The submersible pump replaces Navien’s pump-inlet hose; keep the A and B connections as drawn. |
| Chemical | Includes one quart of branded solution | Diluted cleaning solution; this brand is not named | Kit compatibility advertising is not heater-maker chemical approval. |
| Bucket size (no-solution kit) | Amazon: 3.5 gallon bucket. Chromex’s page: 5-gallon bucket | A bucket of 5 gallons or larger | Measure the bucket that arrives. If it holds under 5 gallons, use your own 5-gallon bucket. |
Match the whole model name, including the 2
Navien’s NPE-2 manual cover names six models. An older NPE-180A and an NPE-180A2 are different model names; keep that suffix in every service conversation.
| Rating-label family | Covered by this manual | Boundary |
|---|---|---|
| NPE-180A2, NPE-210A2, NPE-240A2 | Yes | Use the A2-only recirculation-filter notes where specified. |
| NPE-180S2, NPE-210S2, NPE-240S2 | Yes | Do not add A2-only maintenance steps to an S2. |
| NPE-150S2 | Not named on the manual cover | Obtain its applicable manual before applying this chart. |
| NPE-A/S without the 2; NCB; NFC; other Navien series | Outside this reference | Read the code chart for that exact series and revision. |
Accessory wording matters too. The code table attaches an installed-AHU qualification to E438, E740 and E785. Keep that qualification when describing the fault. The words “circulation pump” in E438 do not, by themselves, establish that an A2’s built-in circulation pump has failed.
Every code in Navien’s NPE-2 user manual
Meanings and listed actions below come from manual 20049624A, printed pages 17–18. The last two columns are my safe-limit and buying advice. “Contact support” means Navien Technical Support at 1-800-519-8794.
| Code | Meaning | Model note | Navien says | Owner or pro | Buy anything? | Source |
|---|---|---|---|---|---|---|
| E003 | Ignition failure | No AHU qualification | Ensure the main gas supply valve is open. | With no gas odor, note valve position. If shut for an unknown reason, leave it shut and call a pro. | No igniter purchase established. | 20049624A p.17 |
| E004 | False flame detection | No AHU qualification | Ensure the electrical cord is properly grounded. | A licensed electrician checks grounding. Do not remove the ground pin or open live wiring. | No replacement part established. | 20049624A p.17 |
| E012 | Flame loss | No AHU qualification | Clean the intake air filter; check proper cord grounding. | Use shutdown and cooling precautions for the filter. Grounding diagnosis belongs to an electrician. | Filter maintenance may need no purchase. | 20049624A p.17 |
| E016 | Heat exchanger overheating | No AHU qualification | Clean the cold water inlet filter; flush the heat exchanger. | Drain and isolate under the manual. Ask a licensed professional if any maintenance step is unclear. | Flush equipment only after confirming the task. | 20049624A p.17 |
| E030 | Exhaust overheating; shutdown above 149°F / 65°C flue temperature | No AHU qualification | Clean the cold water inlet filter; flush the heat exchanger. | Do not bypass the temperature protection. Use qualified service for a recurring overheat condition. | Maintenance equipment may be relevant; no guaranteed cure. | 20049624A p.17 |
| E031 | Burner overheating | No AHU qualification | Contact support. | Leave burner inspection and combustion diagnosis to a qualified service professional. | Diagnose before ordering parts. | 20049624A p.17 |
| E046 | Abnormal limit-control operation | No AHU qualification | Contact support. | Do not bypass a limit control to restart the heater. Record the complete display for service. | No owner-selected replacement established. | 20049624A p.17 |
| E047 | Exhaust thermostat thermistor open or short circuit | No AHU qualification | Contact support. | A qualified professional checks the sensor circuit and its connections; the label alone is not a parts test. | Diagnose the circuit before parts. | 20049624A p.17 |
| E060 | Abnormal dual-venturi operation | No AHU qualification | Contact support. | Keep the cover and combustion adjustments for qualified service; do not alter the venturi. | No maintenance-kit remedy established. | 20049624A p.17 |
| E109 | Abnormal fan-motor operation | No AHU qualification | Clean the intake air filter. | Turn off, disconnect power and allow cooling for maintenance. A returning fault needs service. | Do not select a fan from this code alone. | 20049624A p.17 |
| E110 | Abnormal air pressure | No AHU qualification | Check for exhaust obstruction; clean the intake air filter. | Observe accessible terminations from a safe position. Vent correction, roof access and combustion testing need a pro. | No pressure-sensor purchase established. | 20049624A p.17 |
| E407 | Hot water outlet thermistor open or short circuit | No AHU qualification | Contact support. | A professional tests the outlet sensor circuit; record this exact code rather than reporting only “sensor fault.” | Diagnose before ordering a thermistor. | 20049624A p.17 |
| E421 | Cold water inlet1 thermistor open or short circuit | No AHU qualification | Contact support. | Keep inlet1 distinct from inlet2 when calling. Leave internal electrical checks to qualified service. | No part selected by this chart. | 20049624A p.17 |
| E432 | Cold water inlet2 thermistor open or short circuit | No AHU qualification | Contact support. | Report inlet2 as printed. It is a different entry from E421, even though both concern inlet temperature sensing. | Confirm the circuit before a replacement. | 20049624A p.17 |
| E434 | Abnormal water-adjustment-valve operation | No AHU qualification | Contact support. | Do not force an internal valve or use repeated resets as a substitute for diagnosis. | No valve purchase established. | 20049624A p.17 |
| E438 | Abnormal circulation-pump operation | Installed AHU qualification | Check whether the circulation pump operates properly. | Have a qualified professional identify the relevant pump and AHU arrangement before testing. | Do not assume the built-in A2 pump failed. | 20049624A p.17 |
| E439 | Abnormal flow-sensor operation | No AHU qualification | Contact support. | An internal flow-sensor diagnosis is different from checking whether a faucet is open far enough. | No sensor purchase established. | 20049624A p.17 |
| E441 | Hot water inlet2 thermistor open or short circuit | No AHU qualification | Contact support. | Retain “hot water inlet2” in the service notes. Do not substitute the outlet-sensor definition for E407. | Confirm the circuit before parts. | 20049624A p.17 |
| E445 | Abnormal bypass mixing-valve operation | No AHU qualification | Contact support. | Leave the internal bypass mechanism and connections to qualified service. | No mixing-valve purchase established. | 20049624A p.17 |
| E515 | Abnormal PCB operation | No AHU qualification | Ensure the electrical cord is properly grounded. | An electrician assesses grounding; a qualified service professional diagnoses the board. Do not open live equipment. | Do not order a PCB solely from E515. | 20049624A p.17 |
| E517 | Abnormal DIP-switch setting | No AHU qualification | Contact support. | Record the display. Do not copy switch positions from another heater or internet photograph. | A setting fault does not establish a failed part. | 20049624A p.17 |
| E593 | Abnormal front-panel-key operation | No AHU qualification | Contact support. | Report which control was being used when the code appeared. Leave panel testing to service. | No panel replacement established. | 20049624A p.17 |
| E594 | Abnormal EEPROM operation | No AHU qualification | Contact support. | Record the complete fault and any recent power interruption. Do not attempt memory or firmware modifications. | Diagnose before any board order. | 20049624A p.17 |
| E615 | Abnormal input and memory operation | No AHU qualification | Contact support. | Keep the code in the service record; it does not identify an owner-serviceable memory component. | No replacement part established. | 20049624A p.17 |
| E736 | Abnormal cascade communication | Cascade communication entry | Contact support. | Tell service whether multiple heaters are linked. Leave inter-unit wiring and settings to the professional. | No cable or board purchase established. | 20049624A p.18 |
| E740 | Abnormal outdoor-temperature-sensor operation | Installed AHU qualification | Contact support. | Mention the AHU and outdoor-sensor setup when calling. Do not use an unrelated thermostat code chart. | Diagnose the qualified accessory circuit first. | 20049624A p.18 |
| E760 | Flushing/service alarm | No AHU qualification | Contact the installer for routine service. | Arrange the applicable maintenance. Ask what work is due rather than assuming a failed component. | Equipment only for the confirmed service task. | 20049624A p.18 |
| E762 | Vent pipe not properly inserted | No AHU qualification | Contact support. | Leave vent insertion and sealing to qualified service; do not push or tape the pipe as a reset fix. | No flush-kit remedy established. | 20049624A p.18 |
| E773 | Using the wrong gas | Gas-type entry | Contact support. | Keep gas-type verification and combustion work with a qualified gas professional. Do not adjust switches. | No owner parts order established. | 20049624A p.18 |
| E782 | Abnormal main-panel communication | Main-panel communication entry | Contact support. | A qualified professional checks the communication path; do not reseat internal connectors while powered. | Diagnose before ordering a panel. | 20049624A p.18 |
| E785 | Abnormal flow-switch/sensor operation | Installed AHU qualification | Contact support. | Report the AHU qualification with the code. Do not automatically treat this as the E439 flow-sensor entry. | Confirm the accessory and circuit first. | 20049624A p.18 |
| E788 | Gas-type setting discrepancy between panel DIP switch and panel | Gas-type configuration entry | Check supplied gas type and match the panel/DIP-switch gas setting. | That matching step belongs to a qualified gas professional. No homeowner switch-setting walkthrough. | No replacement part established by the code. | 20049624A p.18 |
| Display condition | Safe next step | Purchase gate | Source |
|---|---|---|---|
| No code | Use the symptom table below; the code chart does not diagnose an unreported fault. | No purchase established. | Navien manual §5.1 p.16 |
| Code absent, including 598-00 / E598 | Photograph the full display and contact support with the complete model and serial. | Do not apply a different series’ definition. | Not in Navien manual §5.2 pp.17–18 |
How to reset without hiding the fault history
Navien identifies the Back button as the reset control. Read and record the code first; an error that disappears from the screen has not explained its own cause.
- 1Check for an emergency
With gas odor, leave and follow the gas-supplier instructions above. With a CO alarm, get outside to fresh air and call emergency services. Do not stay to reset, unplug or investigate the heater.
- 2Record the complete display
Photograph the code, including any suffix, when safe. Note whether hot water was running and whether this fault has returned. Keep the model and serial from the rating label with the photograph.
- 3Use the code-specific next step
For a gas, vent or internal electrical fault, call the appropriate professional. For a permitted maintenance task, follow Navien’s shutdown, cooling and isolation instructions. A reset does not replace those precautions.
- 4Use Back when a reset is appropriate
The manual says to press Back. It gives no universal button-hold duration for this step. If resetting does not solve the issue, refer to the troubleshooting section or contact Navien at 1-800-519-8794.
E003 returning after a reset still means ignition failure, not a confirmed bad flame rod. E110 returning still requires attention to the air path. Keep the earlier photographs: the sequence can help a professional distinguish a recurring fault from a different code that appeared after maintenance.
Do not use the reset button as a way to keep a heater running through E762, E773 or E788. The manual routes those entries to vent or gas-setting checks. A qualified professional must address that work before the heater is returned to normal service.
Separate the air filter from the water filters
E012, E109 and E110 mention the intake air filter. E016 and E030 mention the cold water inlet filter and flushing. Buying a pump for the first group mixes up two different paths.
| Path | What Navien names | Preparation and limit | What to report if it returns |
|---|---|---|---|
| Intake air | Intake air filter; cleaning interval every 3–4 months | Turn off, disconnect power and allow cooling. Follow §4.5; dry the rinsed filter completely before reassembly. | Code, filter condition, whether accessible exhaust appears obstructed. |
| Water inlet | Cold water inlet filter; A2 recirculation inlet filter where applicable | Follow §4.2 draining first: power off, gas shutoff, inlet-water shutoff and pressure drainage through open hot faucets. | Whether the filter contained debris and whether flow changed after correct reassembly. |
| Electrical grounding | Properly grounded power cord for E004, E012 and E515 | Use a licensed electrician. Do not open live wiring, remove a ground pin or add an ungrounded adapter. | Exact code and any known outlet or wiring work. |
| Exhaust and vent | E110 obstruction; E762 insertion | Observe safely accessible outlets only. Leave correction, vent joints and combustion checks to qualified service. | Visible obstruction or damage without attempting a vent repair. |
Navien’s filter-cleaning instruction does include front-cover removal for the air filter. That does not open the rest of the cabinet to general troubleshooting. Keep hands away from internal wiring and gas components. If access is uncertain, stop and have a qualified service professional perform the cleaning.
Water-filter removal is different because the heater must drain first. The A2 procedure includes a recirculation inlet filter and pump drain plug; those notes are marked A2 only. Do not search an S2 for an A2-specific drain point or loosen an unfamiliar fitting to imitate the drawing.
Before connecting a flush kit
Use the exact heater instructions and the pump’s own instructions together. If you cannot reconcile the two, a licensed professional should perform the maintenance.
| Preparation check | What must be established | Stop when |
|---|---|---|
| Bucket | Navien calls for a bucket of at least five gallons. Both selected Chromex pages list that capacity. | You have only a smaller pail or cannot contain the returning liquid. |
| Hoses and pump | Navien lists three hoses and shows a pump inlet. Both kits list two hoses and a submerged pump. | You cannot identify the isolation/service ports. |
| Cleaning solution | Check heater compatibility, dilution, material limits and the chemical label’s PPE and ventilation instructions. | You have no current cleaner instructions or approval for the intended installation. |
| Heat and power | Navien requires power off, disconnected supply and cooling. Follow its isolation sequence before opening a service port. | The heater is hot, power cannot be safely isolated or water pressure has not been relieved as instructed. |
| Time and rinse | Navien specifies at least 45 minutes of circulation followed by its five-minute water rinse. | You cannot complete the rinse or restore the correct valves and filters under the manual. |
The service-port layout must match the work, not just the hose threads. Navien labels valves A, B, C and D in its flushing drawing. A kit’s general instructions cannot identify which valve on your installation isolates the household plumbing. Have a professional resolve that before chemical circulation.
The manufacturer’s drawing also shows why a two-hose submersible kit fits. The third hose in Navien’s list only feeds a pump outside the bucket. Keep the A and B connections as drawn.
Navien’s procedure calls for cleaning solution diluted with water, and each Chromex kit supplies its own formula. Follow that formula’s label, with the specified eye/skin protection and ventilation. Do not mix products or circulate a cleaner whose compatibility is uncertain.
Gather the model, serial, complete code and maintenance records. Confirming that the next job is descaling comes before choosing a hose layout.
Navien calls flushing somewhat complicated and directs unsure readers to an authorized technician or licensed professional. Missing or unidentified service valves are a reason to stop.
No code, but no hot water
Navien’s basic troubleshooting table treats no-flow and cold-water symptoms separately. Start with the symptom you actually have instead of assigning an error code that is not on the display.
| Symptom | Manual check | Safe limit |
|---|---|---|
| No water from the hot tap | Check cold inlet filter, displayed errors, possible freezing and hot/cold shutoff-valve positions. | Do not force a frozen pipe or loosen a pressurised filter. Suspected freeze damage needs qualified assessment. |
| Water stays cold | Check the inlet filter and open the hot faucet fully; §5.1 asks whether flow reaches 0.5 GPM. | That printed threshold is not a universal diagnosis for every A2 operating mode. Do not alter installer settings from this symptom alone. |
| Long wait for hot water | Check whether external recirculation is in use; the manual discusses the return-line arrangement. | A recirculation design or configuration change is professional work, not an automatic pump failure. |
| Water too hot or not hot enough | Check the displayed temperature setting; the manual also lists cross plumbing for insufficient heat. | Scalding risk comes first. Do not enable commercial temperatures to mask an unresolved flow or plumbing fault. |
If opening the faucet further changes the symptom, report that observation rather than declaring a failed flow sensor. E439 is a displayed flow-sensor fault; a low-demand symptom with no code is a different starting point. A professional can use the model and operating mode to choose the next test.
If more than one fixture is affected, note which ones and whether the display changes during the event. Keep that observation separate from the diagnosis. Our no-hot-water troubleshooting guide covers other household causes.
A code is missing, or the heater is an older model
An absent code is a reason to obtain the right documentation. It is not permission to convert a forum explanation into a repair instruction.
598-00 and E598 are not in Navien’s NPE-2 code chart. Record every character, the exact model and any recent service. Ask Navien for guidance for that unit and its current controls. Navien support can tell you what that display means on your unit.
CPSC recall 19-057, dated December 20, 2018, names specified older NPE-180A, NPE-180S and NCB-180E units associated with propane conversion. Those model names lack the A2/S2 suffix. A matching brand name alone does not identify a recalled heater; compare the complete model and manufacturing information.
The CPSC notice tells owners of affected propane units to stop using them and contact Navien for the remedy. If your label instead names an A2 or S2, do not transplant that older recall’s model coverage. Use the exact model and serial when asking Navien about current safety notices.
| Have ready for service | Why it helps |
|---|---|
| Complete model and serial | Identifies the heater and distinguishes A2/S2 from older A/S models. |
| Full code photograph | Preserves suffixes or unfamiliar characters rather than a shortened remembered code. |
| Purchase date and installation location/type | Information requested in Navien’s service instructions. |
| What happened before the code | Hot-water demand, recent maintenance and whether reset changed the display are useful observations. |
| What you safely checked | Prevents the next person from assuming a filter, gas or grounding check has already been performed. |
Questions about Navien codes and maintenance
What does E003 mean on an NPE-240A2?
E003 means ignition failure in Navien’s NPE-2 user manual. The listed first check is whether the main gas supply valve is open. If you smell gas, leave and call the supplier from a neighbor’s phone; do not operate switches or reset the heater.
With no gas odor, note the valve position. Leave a valve closed if its shutdown reason is unknown. Ignition failure alone does not prove that the igniter, flame rod or gas valve needs replacement.
Why does E003 come back after resetting?
A returning code means the underlying ignition fault still needs attention. The user manual does not identify a single failed part from E003. Give the code history and gas-valve observation to a qualified service professional; leave gas-pressure and combustion measurements to that professional.
How do I reset a Navien NPE-A2 or NPE-S2?
Navien’s manual says to press the Back button. Check for hazards and record the error first. It does not give a universal hold-for-several-seconds instruction for this reset. If resetting does not solve the problem, use the troubleshooting instructions or contact Navien at 1-800-519-8794.
What is the difference between E109 and E110?
E109 is abnormal fan-motor operation; Navien lists intake-filter cleaning. E110 is abnormal air pressure; Navien lists an unobstructed exhaust and intake-filter cleaning. Shut down, disconnect power and allow cooling before filter maintenance. A returning code or a vent defect needs qualified service, not an assumed fan replacement.
Can intake-filter cleaning resolve E012?
Cleaning is one listed action for E012, but Navien also calls for proper electrical grounding. Do not promise that a clean filter cures flame loss. Use the manual’s cleaning precautions and have a licensed electrician assess grounding. Persistent flame loss needs a qualified service diagnosis.
Does E760 mean a component has failed?
E760 is labelled a flushing/service alarm. Navien directs the reader to routine service by the installer. It does not identify a failed PCB, pump or thermistor. Confirm the maintenance due before choosing equipment; the service alarm alone does not approve a particular descaling chemical.
Does E438 mean the A2 built-in pump needs replacement?
Navien’s chart lists abnormal circulation-pump operation “in case of installed AHU.” It says to check pump operation. Have the professional identify the relevant pump and accessory arrangement before testing. The code alone does not show that the built-in A2 pump failed.
What should I do about 598-00 or E598?
Neither appears in Navien’s NPE-2 code table (manual 20049624A). Photograph the entire display and contact Navien with the model and serial. Obtain guidance for the installed controls. A code definition from another series or a forum report is insufficient evidence for a repair or parts order.
Why does the water turn cold at low demand without a code?
Navien’s basic table asks whether the hot tap is open enough and whether the inlet filter is clean. It references 0.5 GPM, but operating modes and the exact model still matter. Record whether opening the faucet changes the symptom. Do not declare a failed E439 flow sensor when no E439 is displayed.
Does a two-hose flush kit include everything Navien specifies?
Yes, for the hose count. Navien lists three hoses because its drawing uses a pump outside the bucket. A submersible pump sits in the bucket, so the two Chromex hoses cover the A-valve drain and the pump-to-B-valve feed. The two kits with solution meet the five-gallon bucket minimum; the no-solution kit’s Amazon listing gives a 3.5 gallon bucket, so measure it. Check the cleaner label against your heater before use.
Can I follow a kit’s thirty-minute flush claim?
Use the heater’s applicable procedure. Navien’s instructions require at least forty-five minutes of circulation and a five-minute water rinse. A kit’s general marketing claim does not shorten those intervals or replace Navien’s valve sequence. If the chemical instructions cannot be reconciled with the heater, stop and seek qualified guidance.
Which cleaner should I use to flush a Navien NPE-A2?
Navien’s NPE-2 manual says a cleaning solution diluted with water, without naming a brand. Ask your installer or Navien support which one suits your heater, use a bucket of at least 5 gallons, and circulate for at least 45 minutes.
Why trust this reference, and how we chose equipment
Why trust PlumbingPicks
Isaac Daniels, licensed journeyman plumber in Georgia, is responsible for this reference. This chart follows Navien manual 20049624A, including its model scope and AHU notes. The code meanings come from that manual; the safe-limit advice is mine.
How we pick
We matched the Chromex equipment descriptions to the manual’s maintenance requirements and checked Amazon’s offer records on Oct 22, 2026, 5:00 PM EDT: all three kits were new and in stock. The choices address hose access and the cleaner you plan to use.
CPSC lists no recall for Chromex. We do not turn manufacturer horsepower into an invented cleaning-performance score or claim that a code proves a particular part failed.
| Evidence check | Rule applied |
|---|---|
| Code meaning | Use Navien user manual 20049624A only; no extrapolated unknown-code definitions. |
| Pump and chemical fit | Explain why a submersible pump needs two hoses, and make no claim of Navien chemical approval. |
| Offer eligibility | New and in stock, exact branded kit and matching Amazon image. |
| Claims and ratings | No fabricated use, customer ratings or numerical cleaning scores; no manually entered prices. |
Sources
- Navien, NPE-2 User’s Information Manual, 20049624A, version 1.0: cover models and gas warning; §3.3 p.10; §§4.1–4.5 pp.11–14; §5.1 p.16; §5.2 pp.17–18; back-cover service information.
- Chromex Tools, Tankless Water Heater Flushing Kit, Complete 6-Piece Set; standard one-quart kit product page, read October 20, 2026.
- Chromex Tools, Tankless Water Heater Flush Kit with Right Angle Hoses; product page and one-quart right-angle equipment article, read October 20, 2026.
- Chromex Tools, Tankless Water Heater Flush Kit – Use Your Own Solution (DIY), SKU CXT1-1102 (chromextools.com): 5-gallon bucket with lid, 1/6 HP submersible pump, two 6 ft steel hoses, 2–3 gallons of vinegar or descaler. Read Oct 22, 2026, 5:00 PM EDT.
- CPSC, Navien Recalls Tankless Water Heaters and Boilers Due to Risk of Carbon Monoxide Poisoning, recall 19-057, December 20, 2018.
- CPSC, Carbon Monoxide Information Center; Health Canada, Carbon monoxide: Preventing exposure, alarm-response section: leave immediately for fresh air and call emergency services from outside.
- Amazon offers for the three kits named on this page (Chromex CXT1-1102): new and in stock, with image URLs, Oct 22, 2026, 5:00 PM EDT. The CXT1-1102 listing gives a 3.5 gallon bucket. Availability can change.
